• -35%
Honeywell NFXI-ASD12-HS FAAST-LT suction system P / 1-channel…
search
  • Honeywell NFXI-ASD12-HS FAAST-LT suction system P / 1-channel…

Notifier by Honeywell NFXI-ASD12-HS FAAST-LT suction system P /…

FAAST-LT suction system P / 1-channel analog loop / 2 ID60 and ID3000 compatible detector
star star star star star
€2,064.01 €3,175.40 Save 35%
Tax included
Reference NFXI-ASD12-HS
Quantity
Available in 24/48h

Free shipping
Honeywell NFXI-ASD12-HS FAAST-LT suction system P / 1-channel…

Notifier by Honeywell NFXI-ASD12-HS FAAST-LT suction system P /…

€2,064.01 €3,175.40 Save 35%

Notifier by Honeywell NFXI-ASD12-HS. FAAST-LT suction system P / 1-channel analog loop / 2 ID60 and ID3000 compatible detector Sistema de aspiracion faast-lt p/ lazo analogico de 1 canal/2 detectores compatible id60 e id3000.

Features

FAAST-LT system for fume analysis by aspiration of a channel / IP65, with direct connection to the NOTIFIER loop model NFXI-ASD12-HS with built-in isolator and local supervised siren output per channel, which includes an addressable control module (01- 159) on the door to monitor power and / or flow failure and two VIEW point sensors with 9 alarm levels and sensitivity prealarms that can be parameterized from the analog detection center. System information by means of a pendulum-shaped graphic bar with 9 air flow levels to verify that the air flows according to the requirements of EN54-20. Internal point detectors that incorporate manual and automatic test functions and decadic addressing (01-159) easily replaceable.

  • Internal record of 2,244 events. Principle of dust discrimination by AWACS ™ algorithms.
  • Includes easy access internal filter (FL-IF) and ultrasonic flow sensor.
  • Configuration via standard USB cable and PipeIQ LT software (included).
  • Compatible with OPAL protocol 159 + 159 (shows speed / flow values ??per channel in Pearl) and clip 99 + 99 ID60 / ID3000.
  • It has 2 sample pipe entries per channel Max. 50 meters each, in a single line of 100 meters and 160 meters in T with up to 18 holes per channel in class C, 6 in class B and 3 in class A.
  • Requires 24 Vdc power supply according to EN54-4. Maximum current consumption: 360mA at 24 Vdc (without sirens and supplied with software justifying design and configuration PipeIQ LT.

- NOTIFIER-275