Kilsen KFP-CF2-21 - 2 Zone Conventional Fire Alarm Panel, 2 Acoustic siren…
2 Zone Conventional Fire Alarm Panel - 2 Acoustic siren outputs - 2 alarm and failure outputs - Up to 32 detectors per zone
star
star
star
star
star
Reference
KFP-CF2-21
You might also like
- KILSEN
- Conventional fire alarm panel of 2 zones
- Certificate EN54-2 and EN54-4
- 2 independent siren outputs
- 2 auxiliary alarm and fault outputs
- Capacity to connect repeaters for networking
- Capacity for 2 12V 7.2Ah batteries
Features
- 2 Zone Conventional Fire Alarm Panel
- 2 Acoustic siren outputs
- 2 alarm and failure outputs
- Up to 32 detectors per zone
Specs
Primary power supply | Switching source 230V AC 50-60 Hz 2A max. |
Backup power supply | 2 batteries 12VDC (up to 7.2 Ah). Ensures minimum 120 hours duration. |
Number of zones | 2 zones, up to 32 detectors by area. (20 det. maximum of the range Dx700) |
Siren outputs | 2 Acoustic siren outputs 24VDC monitored max. 250mA |
Relay outputs | 1 alarm output and 1 failure output. All support 28VDC 2A max. |
Extra inputs | 2 |
End of line resistance | Areas fully monitored by end-of-line resistance (4.7K) |
Auxiliary Output Voltage | 24VDC and 250mA max. |
Protection Index | IP30 |
Temperature | -5ºC~+50ºC |
Material and colour | ABS, colour: White |
Dimensions | 435 x 320 x 129 mm |
Weight | 2.8Kg |
Recommended cable | Fire cable with a minimum section of 1.0mm (18AWG). |
Package content
- Panels
- Battery cables
- Fusible
- End of line resistors
Data sheet
- Weight
- 2.8Kg
- Dimensions
- 435 x 320 x 129 mm
- Temperature
- -5º,C~+50º,C
- Siren outputs
- 2 Salidas de sirena 24VDC monitoreadas max. 250mA
- End of line resistance
- Zonas totalmente monitoreadas por resistencia de final de lí,nea (4.7K)
- Material and colour
- ABS, colour: White
- Recommended cable
- Cable de fuego con una secció,n mí,nima de 1.0mm (18AWG).
- Alimentació,n Secundaria
- 2 baterí,as 12VDC (hasta 7.2 Ah). Asegura mí,nimo 120 horas de duració,n.
- Nú,mero de Zonas
- 2 zonas, hasta 32 detectores por zona. (20 det. má,ximo de la serie Dx700)
- Salidas de relé,
- 1 Salida de Alarma y 1 Salida de fallo. Todas admiten 28VDC 2A má,x.
- Entradas extra
- 2
- Tensió,n de Salida Auxiliar
- 24VDC y 250mA max.